Case Studies

Temporary Computer Suite Cooling At The Big Data Institute Oxford

Temporary Computer Suite Cooling- The Challenge

This was a very interesting and sensitive project that required a careful approach and much planning for temporary computer suite cooling.

The Big Data Institute’s server room at Oxford University required critical works to the cooling system to be carried over a weekend. To facilitate this, the fixed cooling system was to be completely shut down.

Temporary AHU hire installed at the Big Data Institute, Oxford.

The Solution To Temporary Computer Suite Cooling

We designed a full Nplus1 replacement system with power generation for this project.

Focussing the design for 100% (Nplus1) redundancy was important to ensure that the client was comfortable with this temporary computer suite cooling project going ahead.

Due to the sensitivity and space restrictions in the work area a decision was made early to locate all the mechanical services externally. Major advantages included, freeing up internal work space and excluding water from the room.

Two overlapping stand alone systems were installed, each consisting of an ACR 160.120 AHU with a 150kw chiller for cooling. Both were specified to maintain the full cooling load- in this way, if any one system was to fail, full operation would be maintained by the other (nplus1 operation).

Envisaging an element of free cooling due to the season, a full fresh air supply was utilised (no recirculated) with the chillers supplying additional cooling as required. The supply air temperature was maintained at 16 degrees.

Supply air was delivered to the computer suite with 500mm flexible ducts which were moved as required by the engineers.

Summary

Overall this temporary computer suite cooling system proved to be a very effective and efficient.

Reassuringly for the customer, the the design included fail safe options which meant that they were comfortable with the works proceeding.

Ultimately, they were very happy with the delivery and operation of the project which was very satisfying for the ACR team.

The ducting installed into the room. Using flexible ducting was great for flexibility. It could be moved to work around and directed towards any problem areas- simple but affective and no water in the room..

A Short Walk Around Video of this Temporary Computer Suite Cooling

Products Used In This Case Study

150kw Chiller Unit Hire (Packaged)
150kw Chiller Unit Hire (Packaged)

Our 150KW commercial and industrial chillers are available for immediate hire.

View Product
160kw HVAC AHU Hire
160kw HVAC AHU Hire

The ACR 160kw HVAC AHU hire unit is a portable air handling unit that can provide automated heating and cooling ventilation for large spaces.

View Product
Air Sock and Ductwork Hire
Air Sock and Ductwork Hire

ACR maintains large stocks of air sock distribution systems for immediate hire. These can be supplied with air handling units for all large and small space climate control applications.

View Product
Chilled Water Hose Hire
Chilled Water Hose Hire

Temporary chilled water hose and ancillaries rental from Advanced Climate Rentals.

View Product

How We've Helped Others In Your Sector

Ventilation Hire and Cleanroom Cooling for Alcatel Submarine Networks
Ventilation Hire and Cleanroom Cooling for Alcatel Submarine Networks

It’s safe to say this ranks among one of our most challenging projects. Albeit, not in terms of scale, but more from a controls point of view. The client’s plant was to undergo a replacement programme.

View Industry
Emergency Server Room Cooling For London Data Centre
Emergency Server Room Cooling For London Data Centre

To provide emergency server room cooling during un-planned repair works. Critically, the area required fast installation of a cooling system to maintain seem-less operation.

View Industry
Temporary Patch Room Cooling in a Data Centre
Temporary Patch Room Cooling in a Data Centre

To provide temporary patch room cooling hire for a major data centre operator. This client was experiencing problems with one of their fixed units and required a temporary system to be installed for secure operation.

View Industry
Chiller Hire for Government Offices/ Data Centre
Chiller Hire for Government Offices/ Data Centre

To supply temporary data centre chiller hire to support a critical government building. ACR were approached by a long term client with an emergency situation.

View Industry
Data Centre Cooling Rental During a Major CCU Refit
Data Centre Cooling Rental During a Major CCU Refit

ACR was contracted to supply temporary data centre cooling rental whilst a major CCU replacement programme was carried-out.

View Industry
24/7
24/7 CALL-OUT 07976 329294
EMAIL US [email protected]